+91 9959 10 11 22

jkpowerengineers@gmail.com

Power Distribution System

SPECIFICATION FOR STANDARD GCU PANEL 600-625kVA

Cubicle type, floor mounting control panel with hinged doors, un-drilled bottom gland plate, AL. Bus Bar and accommodating the following:

SWITCH GEARS
1000A, 3 Pole ACB EDO Type with 185A, 3P neutral contactor for ALTERNATOR

ADDITIONAL FEATURES:
Metering:
Combined Meter for Voltage / Ampere / Frequency
Combined Meter for kW / Power Factor / kVA
Electronic kWH Meter (Counter Display)
Current Transformers

Relay:
Earth Fault Relay (Electronic type)

Indications (LED):
DG ON, Load on DG, Neutral Contactor ON, DC Supply ON,
DG Common Warning, DG Common Shutdown, Mains ON, Battery Charger ON

Push Buttons (GCU BY PASS MODE):

BATTERY CHARGER: (Applicable for AMF Panel only)
SMPS Based Unit with inbuilt Auto/Manual & Float/Boost Facility
DC Voltmeter & Ammeter (Separate)

DOL Starter with Auto Intermittent System for Lub Oil Priming Pump

Microprocessor Based Generator Control Unit (GCU) with following features:
Metering
For Alternator

For Bus / Mains

Other features

2. Protection

3. 16 faults display on GCU LCD Screen.

4. Integrated Automation functions/sequences, through GCU

PLHO / 0712/RKS/ASN